The Amplon RT 1-3 kVA series is an online double-conversion UPS providing consistent sine-wave power to your critical equipment. It supports personal computers, networks, servers, VoIP and telecommunications. The Amplon RT 1-3 kVA series features an output power factor of 0.9 and best-in-class AC-AC efficiency up to 94% resulting in greater energy savings. Optional external battery pack can be connected for longer backup time to keep your applications safe and running smoothly at all times.


Downloads Subscribe Newsletter

Product Introduction

Features & Benefits

Availability

  • True online double-conversion topology and zero transfer time to battery ensure high reliability
  • Watch-dog design of DSP (Digital Signal Processor) increases reliability
  • Cold-start capability provides temporary battery power when the utility power is out
  • Fan failure detection alerts users to failed fans
  • Hot swappable batteries ensure continuous operation even when batteries are being replaced
  • Optional external battery pack for easy scaling of longer backup time
  • Operation temperature tolerance up to 50°C ensures critical loads' continuity
  • High output power factor 0.9 provides more real power to critical loads
 

Green & Low TCO

  • High input power factor (pf > 0.99) and low harmonic distortion (iTHD < 5%) save upstream investment
  • Up to 94% AC-AC efficiency and 97% efficiency in ECO mode result in marked energy cost savings
  • Wide input voltage range reduces the chance of using the battery and extends battery life
  • Intelligent battery management sustains battery life and performance
  • Fan speed control by load level maximizes efficiency and reduces audible noise
 

Flexibility

  • Load segment control allows less-critical loads to be disconnected during blackouts and saves battery runtime for important loads
  • Convertible rack and tower configuration in 2U size cabinet
  • Excellent local communications through rotatable LCD display
  • Intelligent management software connectivity via RS232 or USB port
Applications

UPS N series applications

Specifications
  1. Model
  2. RT-1K / RT-2K / RT-3K

  3. Power Rating
  4. RT-1K: 1 kVA / 0.9 kW
    RT-2K: 2 kVA / 1.8 kW
    RT-3K: 3 kVA / 2.7 kW

  5. Input
  6. Nominal Voltage: 200*/208*/220/230/240 Vac
  7. Voltage range
    175~280 Vac (full load)
    120~175 Vac (70~100% load)
  8. Frequency: 40~70 Hz
  9. Power Factor: > 0.99 (full load)
  10. Current Harmonic Distortion: < 5%

  11. Output
  12. Power Factor: 0.9
  13. Voltage: 200*/208*/220/230/240 Vac
  14. Voltage Regulation: ± 1% (linear load)
  15. Frequency: 50/60Hz ± 0.05 Hz
  16. Voltage Harmonic Distortion: < 2% (linear load)
  17. Overload Capability
    < 105%: Continuous
    105~125%: 1 minute
    125~150%: 15 seconds
  18. Receptacle
    RT-1K: IEC C13 x 6
    RT-2K/3K: IEC C13 x 6, IEC C19 x 1

  19. Efficiency
  20. AC-AC
    RT-1K: 90%
    RT-2K/3K: Up to 94%
  21. ECO Mode
    RT-1K: 96%
    RT-2K/3K: Up to 97%

  22. Battery
  23. Battery Voltage
    RT-1K: 24 Vdc
    RT-2K: 48 Vdc
    RT-3K: 72 Vdc
  24. Typical Backup Time**
    RT-1K: 6.5 minutes
    RT-2K/3K: 7 minutes
  25. Charge Current
    RT-1K: 1.5 A
    RT-2K/3K: 2 A
  26. Recharge Time: 3 hours to 90%

  27. Audible Noise
    RT-1K: < 40 dBA
    RT-2K: < 43 dBA
    RT-3K: < 46 dBA

  28. Display: LCD display and LED indicators

  29. Interfaces: SMART Slot x 1, RS-232 Port x 1, USB Port x 1, REPO x 1

  30. Conformance: CE, TISI, RCM, EAC

  31. Dimensions (W x D x H)
  32. UPS
    RT-1K: 440 x 335 x 89 mm
    RT-2K: 440 x 432 x 89 mm
    RT-3K: 440 x 610 x 89 mm
  33. External Battery Pack
    RT-1K: 440 x 335 x 89 mm
    RT-2K: 440 x 432 x 89 mm
    RT-3K: 440 x 610 x 89 mm

  34. Weight
  35. UPS
    RT-1K: 12 kg
    RT-2K: 18 kg
    RT-3K: 28 kg
  36. External Battery Pack
    RT-1K: 15 kg
    RT-2K: 27 kg
    RT-3K: 44 kg

  37. Environment
  38. Operating Temperature: 0~50°C***
  39. Relative Humidity: 5~95% (non-condensing)

  40. * When the UPS is de-rated to 90% of its capacity.
    ** When the total load reaches 75%.
    *** 40~50°C with 80% de-rating.

    All specifications are subject to change without prior notice.


Run Time
  1. Power Rating Internal Battery External Battery Cabinet Quantity Run time at different load (mins)
    25% 50% 75% 100%
    1 kVA Yes 0 27.0 11.2 6.2 3.8
    1 100.0 48.2 29.8 20.2
    2 174.3 87.1 55.7 39.1
    3 248.7 126.4 82.2 58.6
    2 kVA Yes 0 27.9 11.4 6.3 3.9
    1 102.9 48.8 30.1 20.6
    2 179.1 88.1 56.3 39.9
    3 255.4 127.8 82.9 59.7
    3 kVA Yes 0 33.1 14.2 7.9 5.1
    1 119.2 58.4 36.3 25.2
    2 206.3 104.4 66.9 47.8
    3 293.6 150.6 97.9 70.9
 